datasheetdetails
|
<< | < | AX-HL - Hydrostatic Level Sensor (Clean
|
|
The AX-HL hydrostatic level transmitters are designed to measure the level of clean or contaminated liquids. The pressure sensor at the bottom of the probe measures the sum of the hydrostatic pressure of the liquid column above it. The atmospheric pressure is led to the sensor through a breathing capillary tube, which is equipped with a moisture filter to prevent the moisture reaching and damaging the electronics. Its applications include tank level measurement, borehole level measurement and sewage tank level measurement (with sewage adaptor). |
Product Features
| • Measuring range 1-200m • Temperature compensated
| • Variety of probes available • Easy to set-up
|
Measuring Range
| 1 to 200m
| Linearity
| +/- 0.45%
| Process Temperature
| -10 +60°C
| Power Supply 4-20mA
| 12 to 30Vdc
| Power supply 0-10Vdc
| 18 to 30Vdc - 6mA
| Output (I)
| Two wire HART & 4-20mA
| Output (V)
| Three wire 0-10Vdc
| Intrinsically Safe Class (option)
| ATEX II 1 G Exia B T6
| Cable Length
| Specify at time of order 1 to 200m
| Weatherproof Rating
| IP68
| Materials
| Stainless steel
| Process Connection
| Cable mounting wedge clamp
| Electromagnetic Compatability
| EN61326 Class B
| Probe Dimensions Std
| 173 x 22mm diam
| Probe dimensions Sewage
| 210 x 22mm diam
| Cable Dimensions
| 7mm diam
| Country of Origin
| EU
|
AX-HL.pdf / Hydrostatic Level Transmitter (Clean & Waste Water) | |
|
|
|