Annicom Axio Logo  
    +44(0)1420487788  
 
home | about us | products | datasheets | account
 
   
datasheetdetails
 <<  |  <  |   AX-HL - Hydrostatic Level Sensor (Clean
 Clean water, Polyurethane cable types
AX-HL-C1-5I / Hydrostatic Level Transmitter 1m tank, 5m 2-wire 4-20mA & Hart POA Qty
AX-HL-C2-5I / Hydrostatic Level Transmitter 2m tank, 5m 2-wire 4-20mA & Hart POA Qty
AX-HL-C5-10I / Hydrostatic Level Transmitter 5m tank, 10m 2-wire 4-20mA & Hart POA Qty
AX-HL-C10-15I / Hydrostatic Level Transmitter 10m tank, 15m 2-wire 4-20mA & Hart POA Qty
AX-HL-C1-5V / Hydrostatic Level Transmitter 1m tank, 5m 3-wire 0-10Vdc POA Qty
AX-HL-C2-5V / Hydrostatic Level Transmitter 2m tank, 5m 3-wire 0-10Vdc POA Qty
AX-HL-C5-10V / Hydrostatic Level Transmitter 5m tank, 10m 3-wire 0-10Vdc POA Qty
AX-HL-C10-15V / Hydrostatic Level Transmitter 10m tank, 15m cable 3-wire 0-10Vdc POA Qty
 Waste water, FEP cable types
AX-HL-W1-5I / Hydrostatic Level Transmitter 1m tank, 5m 2-wire 4-20mA & Hart POA Qty
AX-HL-W2-5I / Hydrostatic Level Transmitter 2m tank, 5m 2-wire 4-20mA & Hart POA Qty
AX-HL-W5-10I / Hydrostatic Level Transmitter 5m tank, 10m 2-wire 4-20mA & Hart POA Qty
AX-HL-W10-15I / Hydrostatic Level Transmitter 10m tank, 15m 2-wire 4-20mA & Hart POA Qty
AX-HL-W1-5V / Hydrostatic Level Transmitter 1m tank, 5m 3-wire 0-10Vdc POA Qty
AX-HL-W2-5V / Hydrostatic Level Transmitter 2m tank, 5m 3-wire 0-10Vdc POA Qty
AX-HL-W5-10V / Hydrostatic Level Transmitter 5m tank, 10m 3-wire 0-10Vdc POA Qty
AX-HL-W10-15V / Hydrostatic Level Transmitter 10m tank, 15m 3-wire 0-10Vdc POA Qty
 
  Specify -A for EeX Intrinsically safe
  Specify -xx Specify custom cable length
 <<  |  <  | OVERVIEW | SPECIFICATION | DATASHEETS        

The AX-HL hydrostatic level transmitters are designed to measure the level of clean or contaminated liquids. The pressure sensor at the bottom of the probe measures the sum of the hydrostatic pressure of the liquid column above it. The atmospheric pressure is led to the sensor through a breathing capillary tube, which is equipped with a moisture filter to prevent the moisture reaching and damaging the electronics. Its applications include tank level measurement, borehole level measurement and sewage tank level measurement (with sewage adaptor).
Product Features
• Measuring range 1-200m
• Temperature compensated
• Variety of probes available
• Easy to set-up

Measuring Range
1 to 200m
Linearity
+/- 0.45%
Process Temperature
-10 +60°C
Power Supply 4-20mA
12 to 30Vdc
Power supply 0-10Vdc
18 to 30Vdc - 6mA
Output (I)
Two wire HART & 4-20mA
Output (V)
Three wire 0-10Vdc
Intrinsically Safe Class (option)
ATEX II 1 G Exia B T6
Cable Length
Specify at time of order 1 to 200m
Weatherproof Rating
IP68
Materials
Stainless steel
Process Connection
Cable mounting wedge clamp
Electromagnetic Compatability
EN61326 Class B
Probe Dimensions Std
173 x 22mm diam
Probe dimensions Sewage
210 x 22mm diam
Cable Dimensions
7mm diam
Country of Origin
EU

AX-HL.pdf / Hydrostatic Level Transmitter (Clean & Waste Water)